Check the following items before use.

1.  Check whether the ambient temperature of the VFD during actual application exceeds 40°C, if yes, derate 1% for every additional 1°C. In addition, do not use the VFD when the ambient temperature exceeds 50°C.

Note: For cabinet-type VFD, its ambient temperature is the air temperature inside the cabinet.

2.  Check whether ambient temperature of the VFD during actual application is below -10°C, if yes, install heating facility.

Note: For cabinet-type VFD, its ambient temperature is the air temperature inside the cabinet.

3.  Check whether the altitude of the application site exceeds 1000m. If yes, derate 1% for every increase of 100m; when the installation site altitude exceeds 3000m, consult the local INVT dealer or office.

4.  Check whether the humidity of application site exceeds 90%, if yes, check whether condensation occurred, if condensation does exist, take additional protective measures.

5.  Check whether there is direct sunlight or animal intrusion in the application site, if yes, take additional protective measures.

6.  Check whether there is dust, explosive or combustible gases in the application site, if yes, take additional protective measures.