Motor type | Asynchronous induction motor or synchronous permanent magnet motor |
Voltage | 0 to U1, 3-phase symmetrical, Umax at the field weakening point |
Short-circuit protection | The motor output is short-circuit proof by IEC 61800-5-1 |
Frequency | 0...400Hz |
Frequency resolution | 0.01Hz |
Current | Refer to Ratings |
Power limit | 1.5·PN |
Field weakening point | 10...400Hz |
Carrier frequency | 4, 8, 12 or 15kHz |
To comply with the European EMC Directive (standard IEC/EN 61800-3), use the following maximum motor cable lengths for 4kHz switching frequency.
All frame sizes (with external EMC filter) | Maximum motor cable length, 4kHz |
Second environment (category C3) | 30 |
First environment (category C2) | 30 |
Maximum motor cable length is determined by the drive’s operational factors. Contact the local representative for the exact maximum lengths when using external EMC filters.